227 / 2024-05-20 16:49:32
Investigation on Auxiliary Components of a Spring Operating Mechanism Subjected to Salt-mist and Vibration Circumstance
Spring opearting mechanism,high-voltage circuit breaker,electrical control and auxiliary circiut,salt-mist
全文录用
Hongming Ma / Ltd.;Electric Power Research Institute of Yunnan Power Grid Co.
Kaixuan Zheng / Xi'an Jiaotong University
Jie Zhang / China Southern Power Grid Research Institute
Pengfeng Qiu / Ltd.;Electric Power Research Institute of Yunnan Power Grid Co.
Aohua Zhang / Xi’an Jiaotong University
Xiaofei Yao / Xi'an Jiaotong University
zhiyuan liu / Xi’an Jiaotong University;State Key Laboratory of Electric Power Equipment
The objective of this study is to investigate the impact of Salt-mist and vibration operating circumstances on electrical control and auxiliary circuits of a spring operating mechanism. Four kinds of commonly used electrical control and auxiliary circuit components in the spring operating mechanisms are used, which include the opening coils, the relays, the auxiliary switches, and the terminal connectors. Experimental results showed complex degradation mechanisms. The findings highlight significant increases in contact resistance over salt-mist aging cycles. Vibration aging exacerbates these effects. The study emphasizes the critical necessity for robust mitigation strategies to bolster the reliability of the CBs in complex operating circumstance.